Fixed Type

 

Enos Fixed Type Automatic Transfer Switches are available in 2 or 3 positions, open (break before make) and closed transition
(make before break) configuration.

FEATURES:

Available from 100A to 6300A for Open Transition

  • Tested to IEC 60947-6-1 Standard for Automatic Transfer Switching Equipment
  • ATS Transfer with Center Off Position (A=>0=>B, B=>0=>A)
  • ATS 2 positions transfer (A=>B, B=>A)
  • Electrically operated and mechanical held withinterlock to prevent simultaneously closing of normal and emergency contact
  • Double throw operation using single reliable and field proven solenoid operator
  • Solenoid operator only momentary energised during the transfer
  • Able to be manually operated using maintenance handle in event of solenoid failure
  • Spring transfer mechanism provides virtually friction free, constant force and smooth transfer operations
  • Silver alloy main contacts rated for 100% continuous load carrying and transfer
  • Arc chute to extinguish the arc quickly and safely
  • All components are front accessible for easy inspection and service
  • Last break first make neutral contact minimize transients and reduces nuisance tripping of GFP or ELR
  • Overlapping neutral
  • Compact and simple busbar arrangement for easy termination
  • Protected by comprehensive warranty

 

Available from 200A to 5000A for Closed Transition

  • Neutral pole rating is the same as the phase pole
  • Tested to IEC 60947-6-1 Standard For Transfer Switching Equipment
  • Momentary overlapping of two sources less than 100msec
  • Able to conduct transfer test without interrupting the power to the load
  • Withdrawable transfer switch for faster and easier replacement of transfer switch
  • Utilise reliable and field proven solenoid operator
  • No continuous power consumption, the solenoid operator only momentary energised during the transfer
  • Silver alloy main contacts rated for 100% continuous load carrying and transfer
  • Able to be manually operated using maintenance handle in event of solenoid failure
  • Safety interlock for manual operation can only be achieved using Break Before Make or Open Transition
  • Very Safe and Easy Manual operation using maintenance handle
  • Separate arching contacts to preserve the main contacts from arcs during transfer
  • Arc chute to extinguish the arc quickly and safely 
  • All components are front accessible for easy inspection and service
  • Compact and simple busbar arrangement for easy termination
  • Protected by comprehensive warranty